TSD-1
Universal smoke and heat detector for alarm systems
The TSD-1 is a point detector designed to detect the early stages of a developing fire. For this purpose, it is equipped with a photoelectric sensor of visible smoke, as well as rate of rise temperature sensor. The unique design of the measuring chamber provides high sensitivity and omni-directionality, while a precise Hexamesh stainless steel filter protects the chamber from ingress of contamination and small insects. Detector configuration with DIP-switches and built-in parametric end of line resistors facilitate connection of the detector to virtually any control panel with a 12 V power supply.
- certified by CNBOP Certified Body for compliance with:
- EN 54-7 - smoke detection
- EN 54-5 - heat detection
- unique Swirl chamber for increased smoke sensitivity
- selectable operating mode (smoke, heat, multisensor)
- line type configuration (NO/NC/2EOL) with DIP switches
- precision stainless steel Hexamesh filter
- smoke chamber dirt build-up indicator
- easy installation with detachable base
- compatible with all 12 V alarm panels
- IP code: IP20
The actual appearance of the products may differ from the presented images. Product descriptions are provided in the web service for information purposes only.
quick installer guide
updated: 2025-03-03
442 KB
general information manual
updated: 2022-10-12
407 KB
Other certificates
updated: 2022-11-22
2.78 MB
Declaration of performance
updated: 2022-11-22
848 KB
EU declaration of conformity
updated: 2024-06-17
115 KB
Enclosure dimensions
ø108 x 61 mm
Operating temperature range
-10…+55 °C
Standby mode current consumption
250 µA
Max. current consumption
24 mA
Relay contacts rated load (resistive)
40 mA / 16 V DC
Class according to EN 54-5 (heat sensor)
A1R
Minimum static response temperature
54 °C
Maximum static response temperature
65 °C
Environmental class according to EN50130-5
II